Furnace and heat pump size calculator

A 2,000 sq ft house from the 1970s to 2000s near Chicago loses about 60,000 BTU per hour on a design-cold night (3°F), so it needs an 80,000 BTU furnace at 95% AFUE. Pick your nearest city and house below for a furnace or a heat pump; a Manual J load calculation sets the final size.

R-11 to R-13 walls, some attic insulation, double-pane windows

ASHRAE 99% heating design temperature

Heating load60,000 BTU/hat 3°F outside, 70°F inside
Input rating needed63,200 BTU/hload / 95% AFUE
Furnace to buy80,000 BTUinput; puts out 76,000 BTU/h
Per sq ft30 BTU/hheat loss on a design day

At Chicago's design temperature of 3°F, a 2,000 sq ft 1970s to 2000s house loses about 60,000 BTU per hour. A 95% AFUE furnace needs an input of at least 63,200 BTU/h, so the common size is 80,000 BTU.

Rough estimate: floor area x heat-loss factor x (70°F minus the ASHRAE 99% design temperature). A Manual J load calculation sets the real size.

What size furnace do I need?

Furnace input size (BTU per hour) for a 1970s to 2000s house at 95% AFUE, rounded up to the common size whose output covers the load. Design temperatures are ASHRAE's 99% figures for each city.

House size Houston (34°F)Atlanta (26°F)Washington (21°F)Chicago (3°F)Minneapolis (-6°F)
1,000 sq ft 40,00040,00040,00040,00040,000
1,200 sq ft 40,00040,00040,00040,00060,000
1,500 sq ft 40,00040,00040,00060,00060,000
1,800 sq ft 40,00040,00060,00060,00080,000
2,000 sq ft 40,00060,00060,00080,00080,000
2,200 sq ft 40,00060,00060,00080,00080,000
2,500 sq ft 60,00060,00060,00080,000100,000
3,000 sq ft 60,00080,00080,000100,000120,000
3,500 sq ft 60,00080,000100,000120,000140,000
4,000 sq ft 80,000100,000100,000140,000Over 140,000

Where even the smallest common size, 40,000 BTU input, puts out more than 140% of the load (warm cities, small houses), Manual S would call it oversized; look at a smaller or two-stage furnace, or a heat pump. A newer house needs about 33% less than these figures; an older, drafty one about 44% more.

How many BTU does it take to heat a house?

Heating load in BTU per hour on a design-cold day in Chicago (3°F outside, 70°F inside), by how well the house holds heat.

House size Newer, built to code since about 20101970s to 2000s houseOlder or drafty, little wall insulation
1,000 sq ft 20,00030,00043,400
1,500 sq ft 30,00045,00065,000
2,000 sq ft 40,00060,00086,700
2,500 sq ft 50,00075,000108,400
3,000 sq ft 60,00090,000130,100

The load scales with the gap between inside and outside. Atlanta's design temperature is 26°F, a 44°F gap against Chicago's 67°F, so the same house there needs about 65% of these figures. A furnace size copied from a house in another climate can be far off.

What size heat pump do I need?

Tons of cold-climate heat pump for a 1970s to 2000s house. Where even a 5 ton unit (the largest home size) falls short at the design temperature, the table adds the electric backup heat in kW that covers the rest.

House size Atlanta (26°F)Washington (21°F)Chicago (3°F)Minneapolis (-6°F)
1,000 sq ft 2 tons2.5 tons4 tons5 tons
1,200 sq ft 2.5 tons3 tons5 tons5 tons + 1.1 kW
1,500 sq ft 3 tons3.5 tons5 tons + 1.1 kW5 tons + 4.1 kW
1,800 sq ft 3.5 tons5 tons5 tons + 3.7 kW5 tons + 7.1 kW
2,000 sq ft 4 tons5 tons5 tons + 5.5 kW5 tons + 9.1 kW
2,200 sq ft 5 tons5 tons5 tons + 7.3 kW5 tons + 11.1 kW
2,500 sq ft 5 tons5 tons + 2.0 kW5 tons + 9.9 kW5 tons + 14.1 kW
3,000 sq ft 5 tons + 2.3 kW5 tons + 5.2 kW5 tons + 14.3 kW5 tons + 19.1 kW
3,500 sq ft 5 tons + 5.1 kW5 tons + 8.5 kW5 tons + 18.7 kW5 tons + 24.2 kW
4,000 sq ft 5 tons + 8.0 kW5 tons + 11.7 kW5 tons + 23.1 kW5 tons + 29.2 kW

A heat pump's rating is its output at 47°F, and it loses capacity as the air gets colder. On ENERGY STAR's list of certified models, standard heat pumps keep a median 65% of their rated heat at 17°F. To earn ENERGY STAR's cold-climate label, a model must keep at least 70% at 5°F, and half of the certified cold-climate models keep 78% or more. The calculator uses the 70% floor, so a strong cold-climate model may need a size smaller than shown; check its capacity table at your design temperature (NEEP's cold-climate heat pump list publishes these).

Two numbers decide the backup heat. The balance point is the outdoor temperature where the heat pump's output equals the house's heat loss; below it, electric strips (or a furnace in a dual-fuel setup) make up the difference. DOE draws the house's load as a straight line from the design load down to zero at 65°F. The shortfall at the design temperature, divided by 3,412 BTU per kW, is the backup heat to install. For the default house above, a 5 ton cold-climate unit covers the house down to about 17°F and needs 5.5 kW of strips at 3°F.

What is the design temperature for my city?

The 99% heating design temperature is the outdoor temperature that is colder only 1% of the hours in a typical year (about 88 hours). Load calculations size heating for that temperature, not for the record low. These are ASHRAE's figures, from 1994 to 2019 weather data.

City Weather station 99% design temperature
Miami, FL Miami NHC 53°F
Los Angeles, CA Los Angeles Intl 47°F
Phoenix, AZ Phoenix Sky Harbor 42°F
Las Vegas, NV Las Vegas McCarran 35°F
Houston, TX Houston Bush 34°F
Seattle, WA Seattle Tacoma 30°F
Dallas, TX Dallas Fort Worth 27°F
Atlanta, GA Atlanta Hartsfield-Jackson 26°F
Charlotte, NC Charlotte Douglas 25°F
Washington, DC Washington Reagan 21°F
Nashville, TN Nashville Intl 20°F
New York, NY New York LaGuardia 18°F
Philadelphia, PA Philadelphia Intl 18°F
Salt Lake City, UT Salt Lake City Intl 16°F
Boston, MA Boston Logan 13°F
St. Louis, MO St Louis Lambert 12°F
Columbus, OH Columbus Glenn 10°F
Detroit, MI Detroit Wayne County 7°F
Kansas City, MO Kansas City Intl 7°F
Denver, CO Denver Intl 6°F
Chicago, IL Chicago O'Hare 3°F
Milwaukee, WI Milwaukee Mitchell 3°F
Burlington, VT Burlington Intl -2°F
Anchorage, AK Anchorage Intl -3°F
Minneapolis, MN Minneapolis-St Paul -6°F
Fargo, ND Fargo Hector -14°F
Fairbanks, AK Fairbanks -38°F

Your local building department may set its own design temperature for permits; if it does, use that one in the custom field.

What does AFUE mean?

AFUE (annual fuel utilization efficiency) is the share of the fuel's heat that reaches the house over a season. Furnaces are sold by their input rating, so the heat you get is input x AFUE.

AFUE Heat from 100,000 BTU of gas Input for a 60,000 BTU/h load
80% (standard) 80,000 BTU 75,000 BTU/h
95% (ENERGY STAR, South) 95,000 BTU 63,158 BTU/h
97% (ENERGY STAR, North) 97,000 BTU 61,856 BTU/h

80% is the federal minimum for most indoor gas furnaces made until December 18, 2028, when it rises to 95%. ENERGY STAR certifies gas furnaces at 95% AFUE or more in southern states and 97% or more in northern ones.

How the calculator works

  1. Temperature gap: 70°F inside minus your city's 99% design temperature (the outdoor temperature that is colder only 1% of the hours in a year).
  2. Heating load = heated floor area x heat-loss factor x temperature gap. The factors, in BTU per hour per sq ft per °F, are 0.30 for a newer house, 0.45 for a 1970s to 2000s house and 0.65 for an older, drafty one.
  3. Furnace: input rating = load / AFUE, rounded up to a common size (40,000, 60,000, 80,000, 100,000, 120,000, 140,000 BTU).
  4. Heat pump: tons = load / (12,000 x the share of rated heat it keeps at the design temperature), rounded up to a size from 1.5 to 5 tons. Any shortfall / 3,412 = backup kW.

The heat-loss factors are our estimates, not a published table. The newer-house figure matches DOE Building America's Manual J examples for houses built to the 2009 energy code (about 0.28 in Chicago and 0.33 in Orlando). The 1970s to 2000s figure is worked out from ENERGY STAR's typical-house assumptions for homes of that era: R-11 walls, an R-15 attic, double-pane windows and leaky air sealing come to about 0.43, plus duct losses. Use the custom factor if you have a better number, for example from an energy audit.

When do you need a Manual J load calculation?

Before you buy. ACCA's Manual J adds up each wall, window, ceiling and floor, the air leakage and the ducts, which a square-foot estimate cannot. DOE's Building America guide, following ACCA's Manual S, keeps a furnace's output within 140% of the calculated load. A heat pump in a cold climate may be sized above the cooling load to cover more of the heat, as long as the contractor picks a unit that can turn down for summer.

Sources

Design temperatures: ASHRAE Handbook of Fundamentals 2021 climatic design conditions, via ashrae-meteo.info. Example loads, the balance-point method and Manual S limits: DOE Building America, Strategy Guideline: HVAC Equipment Sizing (Burdick, 2012). Typical 1970s to 1980s house: ENERGY STAR, Seal and Insulate Savings Analysis Baseline Home Assumptions. Federal AFUE minimums: 10 CFR 430.32(e). ENERGY STAR furnace levels: ENERGY STAR Furnaces Key Product Criteria; common input sizes from the ENERGY STAR certified furnaces list. Cold-climate criteria: ENERGY STAR Heat Pump Key Product Criteria; capacity at 17°F and 5°F from the ENERGY STAR certified air-source heat pumps list (284,747 combinations, November 2026); straight-line capacity between test points as in DOE guidance on heat pump performance at 5°F. Sizing approaches for cold climates: PNNL Building America Solution Center, Cold Climate Heat Pump Sizing and Selection. kW to BTU: EIA, British thermal units.

Related calculators

All heating and cooling calculators · More on heating and cooling